| Products> Okken |
|
Architecture>
Busbars
The
main busbar is placed horizontally, all along the
switchboard in a complete segregated compartment,
at the top side.
The system has an original square type layout
offering multiple advantages:
 Limited
EM and thermal radiation
 Compact
space allowing top front connection of the power
cables/ busways
 Favorable
thermal exchange at the busbar level, avoiding
the derating of the CBs
 Increased
electrodynamic withstand |

The main busbar |
The distribution busbar system is
suited to the field configuration type:
 The
fields type 230 have no vertical BB
 The
fields type 115 are composed of copper bars rated
In
according to nb of busbars:
Nb and
cross-section of bars
|
In(A) 35°
ext-IP31
|
1x80x10
|
1700
|
2x80x10
|
2800
|
3x80x10
|
3200
|
3x120x10
|
4000
|
 The fields type 70 are using copper
bars rated:
In
according to nb of busbars:
Nb and
cross-section of bars
|
In(A) 35°
ext-IP31
|
1x40x10
|
1000
|
1x50x10
|
1200
|
1x80x10
|
1700
|
1x100x10
|
2100
|
 The fields type 185 are using copper
bars rated:
In
according to nb of busbars:
Nb and
cross-section of bars
|
In(A) 35°
ext-IP31
|
1x40x10
|
630
|
1x50x10
|
800
|
1x80x10
|
1250
|
1x100x10
|
1500
|
 Nb of bars, supports and cross-members
according to Icw
Depending
on the required system, the Okken system
arrangement has different phase/neutral/PE
configurations (please consult us).
|

The distribution busbars |
|
|
|
|